|
Building Design
Considerations for Drycleaning Plants Operating with ExxonMobil
Chemical Drycleaning Fluid 2000 (DF-2000 Fluid)
|
 |
|
The standards as referenced in this document along with applicable
local building codes should be consulted for specific requirements
but ultimate decisions must be approved by the local "Authority
Having Jurisdiction". This information was developed for DF-2000
Fluid; it may not apply to Stoddard or other petroleum solvents,
which may have different chemical and physical properties.
The National Fire Protection Association's NFPA 32, 2000 Edition (Standard for
Drycleaning
Plants) can be used as a guide for minimal building requirements.
The authority having jurisdiction must issue the permit to construct
and/or operate the hydrocarbon solvent equipment and is the definitive
reference for building requirements.
DF-2000 Fluid is within the NFPA 32 Class III A solvent classification. This
classification is based on the flash point of the solvent being
within the range of 140°F and 200°F. Because of this classification,
the drycleaning plant using DF-2000 Fluid is governed by NFPA 32
guidelines for Class III A plants.
Electrical wiring of a Type III A plant should be in accordance
with NFPA 70 (National Electrical Code) for ordinary locations.
There
may be more stringent requirements for distillation and drying
equipment.
Separation requirements for Type III A Drycleaning Plants are
outlined in Section 6.1.2.1 of NFPA 32 which is quoted below.
Automatic sprinklers are required for such plants unless the
conditions of Exception No. 2 below are met1.
NFPA has just released an errata for NFPA 32 where Section
6.1.2.1 Exception 2 should read as follows:
"(a) Features that limit oxygen concentrations to less
than 8 percent by volume."
(Reprinted with permission from NFPA 32, Drycleaning
Plants, Copyright ©2000,
National Fire Protection Association, Quincy, MA 02269. This
reprinted material is not the complete and official position of the
National Fire Protection Association, on the referenced subject
which is represented only by the standard in its entirety. 1The
printed 10 per cent by volume oxygen concentration in Subpart
(a) is under review by the NFPA since the clause may have been
approved with 8 rather than 10 per cent.)
- References
National Fire Protection Association (NFPA 32), Standard for
Drycleaning Plants.
NFPA 70 - National Electric Code® (NEC), Article 500-501.
NFPA 13 - Standard for the Installation of Sprinkler Systems.

Technical Assistance:

|